PET-70216/ET-7026 User Manual, version 1.0.1 beta1, Page: 112
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]om
C.3. Safe Value
If the time of the Host PC losing Modbus/TCP communication with the module is
greater than the host WatchDog timer setting (called WDT timeout), the output of the
Digital and Analog channels is set to the Safe Value, and the count of the host WDT
events is increased by one.
AO address 40558 is the address of the Host WDT events. The value of the WDT
events will be not stored into EEPROM, and will return to 0 after the module is
rebooted. DO address 00515 is the first address of the Safe value and the total
number of channels depends on the type of module.
For example:
Address 00515 to 00518 records the Safe value for the 4-Channel
ET-7017/PET-7017.
Be careful to set the ON value to DO address 00432 to write the DO Safe value to the
EEPROM of the ET-7000/PET-7000 DO module after using Modbus commands (05
or 15) to change the Power ON value.
While the WDT timeout is set, the module can also receive the Modbus/TCP
commands (05, 06, 15 and 16) to change the DO or AO value without needing to
clear the host watchdog timeout value.
Configuration via Web page
Browse to the homepage of the ET-7000/PET-7000, and click the “Modbus I/O
Settings” link in the Configuration Section of the Main Menu tree.