Installation and Operating Instructions
SDC 306 1316BED036-11B-E Date 06/09
- 28 -
10.1.7 Return line monitor
In the case of solar thermal systems with
auxiliary heating and where there is a heat
station, the return line of the heating circuit
is layered into the storage cylinder.
Depending on the temperature difference
between the return line and the solar
storage cylinder in the middle, a 3-way
valve is triggered in order to layer the return
line at the bottom or centre of the solar
storage cylinder. The heating flow is
connected to the upper part of the solar
storage cylinder.
To prevent the pump from switching on and
off due to only minimal differences in
temperature, a hysteresis is preset.
10.1.8 Thermal transfer
In the case of systems with a storage
cylinder and an additional solar storage
cylinder, this function transfers the water
heated by solar power from the solar
storage cylinder to the conventionally
heated storage cylinder. To prevent the
pump from switching on and off due to only
minimal differences in temperature, a
hysteresis is preset.
10.1.9 Pump block protection
All pumps that have not run for 24 hours are
switched on for approximately 5 seconds
each day between 12.00 and 12.01.
10.1.10 Solid fuel boiler
Activation conditions for the loading pump
are that:
1. the boiler temperature is 5K higher
than the minimum temperature of the
boiler and,
2. the boiler temperature is 5K lower
than the maximum temperature of
the boiler and,
3. the storage cylinder temperature is
5K lower than the storage cylinder
maximum temperature, and
4. the difference between the boiler
temperature and storage cylinder
temperature is higher than the
switch-on hysteresis.
Deactivation conditions for the loading
pump are that:
1. the boiler temperature is lower than
the minimum temperature for the
boiler, or
2. the maximum boiler temperature is
reached, or
3. the storage cylinder temperature has
reached the maximum storage
cylinder temperature, or
4. the difference between boiler
temperature and storage cylinder
temperature is less than the switch-
off hysteresis.
10.1.11 Swimming pool heating/secondary storage cylinder
The second solar consumer “swimming
pool” is operated as per a standard
system (storage cylinder). The
difference between this and a buffer
storage cylinder is a lower hysteresis of
1K.