Installation and Operating Instructions
SDC 306 1316BED036-11B-E Date 06/09
- 52 -
12 R
ECTIFICATION OF FAULTS
There are basically two kinds of system fault:
Faults that are recognised by the control unit and which it can therefore indicate
Faults that cannot be indicated by the control unit
12.1 Faults with error message
Error display Possible causes Action
!
Flashing
Sensor cable
interrupted
Sensor defective
Check cables
Check sensor resistance value,
replace sensor if necessary
!
Flashing
Short circuit in sensor
wiring
Sensor defective
Check cables
Check sensor resistance value,
replace if necessary
Circulation error:
no flow rate
!
+
Flashing
Additionally in the case of
energy yield metering:
Error in pump
connection
Pump defective
Air in the system
Flow rate counter
defective
Connection to flow rate
meter defective
Sensor cable
interrupted
Sensor defective
Check cabling
Replace pump
Bleed system
Check whether, when the system is
running, the impeller wheel of the
meter moves (if visible)
Check cables
Check cables
Check sensor resistance value,
replace sensor if necessary
Legionella error:
no flow rate
+
!
flashing
Error executing anti-
legionella function
Contact your fitter or supplier